1.5 Error Messages

Display
351. 5
CAL
350. 0
Err
351. 5
Err
350. 0
NVx
351. 5
A-d
350. 0
Err
351. 5
9999
350. 0
351. 5
t. E rr
350. 0
351. 5
CJ. F
350. 0
351. 5
rSP. F
350. 0
9999
999
StK
Error/Action
Calibration Error
Turn mains power off and on again
(if the error persists contact the
Customer Support Organization).
Non-volatile Memory Error
x = 1: Processor Board Memory
x = 3: Power Supply Board Memory
Turn mains power off and on again
(if the error persists, check
configuration/setup settings).
A to D Converter Fault
The analog to digital converter is not
communicating correctly.
Input Value Over/Under Range
Auto-tune Error
Number displayed indicates the type
1
of error – see Table 2.1, page 30.
Cold Junction Failed
Cold junction sensor is faulty or has
1
not been fitted correctly.
Remote Set Point Failed
Input value is over or under-range.
Only appears if the remote set point
is displayed or in use.
Position Feedback Fail
Input value is over- or under-range.
Only appears if output type set to
'PFb' – motorized valve with feeback.
Valve Sticking
Motorized valve not moving at the
speed expected. Valve may be
sticking.
1 DISPLAYS AND FUNCTION KEYS...
To clear the display:
Press the
Press the
Contact the Customer
Support Organization
Restore valid input
Press the
Check connections or replace
if faulty.
Restore valid input
Restore valid input
Check that the correct
Regulator Travel Time has
been set – see Section 3.5.
Check the valve.
key
key
key
9