Omron CP1L-EL20DR-D Operation Manual page 576

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Temperature Sensor Units
Note
542
Creating Ladder Program
(1) Write temperature data command
Write temperature data command which read temperature data from input
word to CIO n+1.
(2) Response confirmation
After CP1W-TS004 receives CIO n+1 read command and CP1W-TS004's
internally specified input temperature data is ready, the value which is the
same as the read command will be stored in CIO m+1. The temperature
data will be stored in CIO m+2 at the same time.
(3) Read temperature data
Store the temperature data from CIO m+2 in DM area.
The power is ON
CIO n+1
(1) Write temperature data
command
CIO m+1
(2) Response confirmation
Read command
matches response
CIO m+2
(3) Read temperature data
Store in DM area
Response
7FFE
CIO m+1
Temperature data
7FFE
CIO m+2
Read command
0000
CIO n+1
Power ON
(1) It takes about 2ms maximum until it is reflected to CIO m+1 and m+2 from
writing the read command to CIO n+1.
(2) It takes about 1s after the power is turned ON, till a read command initial
processing of CP1W-TS004 is completed, so a response to the read
command after power ON takes only about 1s. After the power is turned
ON, create a ladder program 1s later due to its control by temperature da-
ta.
(3) When writing a command other than that specified in the temperature
data read command, CIO m+1 and m+2 hold the previous value.
Read command
and response are
unmatched
#9901
Input 1
temperature data
Approx. 1s
Approx. 2ms
#9901
Write input 1
Write input 2
temperature data
temperature data
command
command
Section 9-5
#9902
Input 2
temperature data
2ms max. from writing read
command, response, to reading
temperature data
#9902
#9903