Wiring CP1L-EL/EM CPU Units

3-4
Wiring CP1L-EL/EM CPU Units
3-4-1

Wiring Power Supply and Ground Lines

CPU Units with DC Power Supply

DC Power Supply Wiring
24 VDC
+
+
NC
Note
82
Circuit protector
COM
01
03
05
07
00
02
04
06
GR: Protective ground terminal
Ground (100 Ω or less)
• Use crimp terminals or solid wire for wiring the power supply. Do not con-
nect bare stranded wires directly to terminals.
6.2 mm max.
• M3 self-rising terminal screws are used. Tighten the terminal screws to
the torque of 0.5 N·m.
• To prevent noise, use a ground line of 100 Ω or less.
• Provide a power supply of 20.4 to 26.4 VDC.
• The maximum current consumption is 20 W for CPU Units with 30 or 40
I/O points and 13 W for CPU Units with 20 I/O points.
• When the power supply is turned ON, the inrush current is approximately
five times the normal current.
• The GR terminal is a ground terminal. To prevent electrical shock, use a
dedicated ground line (2 mm
(1) Never reverse the positive and negative leads when wiring the power sup-
ply terminals.
(2) Supply all power to the power supply terminals from the same source.
Upper terminal block
09
11
01
03
05
08
10
00
02
04
6.2 mm max.
2
min.) of 100 Ω or less.
Section 3-4
07
09
11
06
08
10