4.6.3

Voltage and Current Harmonics

This measures the total harmonic distortion rate on voltage and current, as well as
the effective value, the harmonic distortion factor, any continuous harmonic com-
ponent and harmonics up to the 50th.
First Function: VOLTAGE HARMONIC MODE
There are 52 measurement pages in this mode. Use the ◄► buttons to move
through them.
ITEM
1st Page
1.
Rate of total voltage
harmonic distortion (VTHD-F,
also noted as VTHD)
2.
Root mean square value
(Vrms)
3.
Voltage distortion factor
(VTHD-R, also noted as VDF)
4.
Power Quality Analyzer Model 8220
Figure 4-16
2nd Page
Number of voltage
harmonic considered
The continuous harmonic
component value
Percentage of the continu-
ous value compared with
the effective fundamental
value
# of page displayed / total # of pages
1
2
3
4
3rd Page
Number of voltage
harmonic considered
Effective value of the
harmonic component
considered
Percentage of this
effective value compared
with the effective
fundamental value
41