AEMC 8220 User Manual page 47

Single-phase power quality analyzer
Table of Contents

Advertisement

Step 2:
The display will show the following screen.
The user should then connect the L3 phase to the input (+) of the 8220, within
10 seconds, after which time the following error message
limit exceeded) is displayed. The user must start the sequence again from
the beginning (Step 1).
As soon as the test leads are connected to the circuit, the 8220 automatically
moves to Step 3.
NOTE: If the display indicates
determination of the order of the phases.
This error may be due to one of the following causes:
- The three-phase network frequency is unstable.
- The three-phase network frequency is outside the 40 to 70Hz range.
- The voltage signal is too weak (below 10V
- Operations were incorrectly carried out.
To return to the first Step, press the◄ button.
Step 3:
The display will then show either:
- Correct order of phases: L1-L2-L3
- Incorrect order of phases: L3-L2-L1
Power Quality Analyzer Model 8220
Figure 4-18
(Error) an error has been detected during the
).
RMS
(time
45