Meaning Of Leds On The Sensor Module Cabinet-Mounted Smc20 - Siemens SINAMICS S120 Combi User Manual

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

Encoder system connection
11.1 Sensor Module Cabinet-Mounted SMC20
11.1.3.5

Meaning of LEDs on the Sensor Module Cabinet-Mounted SMC20

Table 11- 4
Meaning of LEDs on the Sensor Module Cabinet-Mounted SMC20
LED
Color
RDY
-
READY
Green
Orange
Red
Green/red
Green/
orange
or
Red/
orange
Cause and rectification of faults
Further information about the causes of faults and how to remedy them may be found in the
manual: SINAMICS S120 Commissioning Manual.
210
Status
Off
Electronics power supply is missing or outside the
permissible tolerance range.
Continuous
The component is ready for operation and cyclic DRIVE-
light
CLiQ communication is taking place.
Continuous
DRIVE-CLiQ communication is being established.
light
Continuous
At least one fault is present in this component.
light
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
0.5 Hz
Firmware is being downloaded.
flashing
light
2 Hz
Firmware download is complete. Wait for POWER ON
flashing
light
Flashing
Component recognition via LED is activated (p0144).
light
Note:
Both options depend on the LED status when component
recognition is activated via p0144 = 1.
Description, cause
Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
Remedy
Remedy and
acknowledge fault
Carry out a POWER
ON