13.6.5

Selecting power supply units

You are advised to use the devices in the following table. These devices meet the applicable
requirements of EN 60204-1.
Table 13- 5
Recommended SITOP Power
Rated output
Phases
current [A]
5
1 / 2
10
1 / 2
20
1 / 2
3
40
1 / 2
3
Note
When using an external 24 V power supply with a continuous current > 20 A, an overcurrent
protection device must be used for the S120 Combi Power Module, the cables and the
busbars. A circuit breaker is recommended as overcurrent protection device.
The tripping characteristic of the circuit breaker depends on
• the loads to be protected and
• the maximum current provided by the power supply unit in the case of a short-circuit.
Table 13- 6
Recommendation for Control Supply Module
Rated output
Phases
current [A]
20
3
See also catalog NC61.
When an external power supply is used, e.g. SITOP, the ground potential must be
connected to the protective conductor system (DVC A).
SINAMICS S120 Combi
Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
Rated input voltage [V]
Working voltage range [V]
120 - 230/230 - 500
85 - 264/176 - 550 AC
120 - 230/230 - 500
85 - 264/176 - 550 AC
120/230
85 - 132/176 - 264 AC
3-ph. 230/400 to 288/500
320 - 550 AC
120/230
85 - 132/176 - 264 AC
3-ph. 230/400 to 288/500
320 - 550 AC
Input voltage range [V]
380 V AC -10% (-15% < 1 min)
to 480 V AC +10%
DC 300 – 800
WARNING
Short-circuit current [A]
Approx. 5.5 (power up),
typ. 15 for 25 ms
(operation)
Approx. 12 (power up),
typ. 30 for 25 ms
(operation)
Approx. 23 (power up),
typ. 60 for 25 ms
(operation)
Approx. 46 (power up),
typ. 120 for 25 ms
(operation)
Short-circuit current [A]
< 24
Cabinet design and EMC
13.6 24 V DC supply
Order number
6EP1333-3BA00-8AC0
6EP1334-3BA00-8AB0
6EP1336-3BA00-8AA0
6EP1436-3BA00-8AA0
6EP1337-3BA00-8AA0
6EP1437-3BA00-8AA0
Order number
6SL3100-1DE22-0AA1