X21/X22 Ep Terminals / Temperature Sensor Motor Module - Siemens SINAMICS S120 Combi User Manual

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

Note
The motor brake must be connected via connector X11 on Single Motor Modules, and X11
and X12 on Double Motor Modules. The BR- cable must not be connected directly to
electronics ground (M).
Only protective extra-low voltages (DVC A) that comply with EN 60204-1 must be
connected to all connections and terminals between 0 and 48 V DC.
The voltage tolerances of the motor holding brakes (24 V ± 10 %) must be taken into
account.
7.3.4

X21/X22 EP terminals / temperature sensor Motor Module

Table 7- 3
X21/X22 EP terminals/temperature sensor
Terminal
1
2
3
4
Max. connectable cross-section 1.5 mm
Type: Screw terminal 1 (see Chapter "Control cabinet installation and EMC / connection system")
NOTICE
The function of the EP terminals is only available when Safety Integrated Basic Functions
are enabled.
SINAMICS S120 Combi
Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
WARNING
Function
+ Temp
- Temp
EP +24 V (Enable Pulses)
EP M1 (Enable Pulses)
2
Motor Modules Booksize Compact as expansion axes
Technical specifications
Temperature sensors: KTY84–1C130 / PTC / bimetallic
switch with NC contact
Supply voltage: 24 V DC (20.4 V - 28.8 V)
Current consumption: 10 mA
Isolated input
Signal propagation times:
L → H: 100 μs
H → L: 1000 μs
The pulse inhibit function is only available when Safety
Integrated Basic Functions are enabled.