Siemens SINAMICS S120 Combi User Manual page 189

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

LED
Color
Fail-safe inputs / double inputs
F_DI z
LED
LED
(input x,
x
x+1
(x+1)+,
Red
(x+1)-)
Red
LED
LED
x
x+1
Green
Green
Green
Green
Inputs x+1 (DI 1+, 3+, .. 19+) can be set individually via parameter p10040 (TM54F).
1)
p10040 (TM54F) = 0: Input x+1 is an NC contact.
p10040 (TM54F) = 1: Input x+1 is NO contact.
Factory setting: p10040 (TM54F) = 0 for all inputs x+1.
Single digital inputs, not fail-safe
DI x
Green
Fail-safe digital outputs with associated readback channel
F_DO y
Green
(0+..3+,
0-..3-)
Readback input DI 2y for output F_DO y (y = 0..3) at test stop.
The status of the LEDs also depends on the type of external circuit.
DI 2y
Green
Cause and rectification of faults
The following reference contains information about the cause of faults and how they can be
rectified:
SINAMICS S120 Combi List Manual
SINAMICS S120 Combi
Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
Status
NC contact / NC contact
Continuous
Different signal states at input x and x+1
light
No signal at input x and no signal at input x+1
NC contact / NO contact
Continuous
Same signal states at input x and x+1
light
No signal at input x and no signal at input x+1
NC contact / NC contact
Continuous
One signal at input x and one signal at input x+1
light
NC contact / NO contact
Continuous
One signal at input x and no signal at input x+1
light
Off
No signal at digital input x (x = 20..23)
Continuous
Signal at digital input x
light
Continuous
Output y (y=0 .. 3) carries a signal
light
Off
One of the two output lines y+ or y- or both lines of
output y carry a signal
Continuous
Both output lines y+ and y- carry no signal
light
Additional system components
10.1 Terminal Module TM54F
Description, cause
: (z = 0..9, x = 0, 2, ..18)
1)
: (z = 0..9, x = 0, 2, ..18)
1)
: (z = 0..9, x = 0, 2, ..18)
1)
: (z = 0..9, x = 0, 2, ..18)
1)
Remedy
187