EDAC Electronics Ltd. EDAC700 RTU Technical Reference Manual page 30

Table of Contents

Advertisement

Note! For code Ver 1.2.8p and below 4 decimal points must be entered. Eg. to enter 30
you must enter 30.0000.
Low alarm set point. Enter the signal level in engineering units that will cause the alarm
condition to reset or stop triggering.
Note! For code Ver 1.2.8p and below 4 decimal points must be entered. Eg. to enter
30 you must enter 30.0000.
*Trig when high (default)
- Trigger when the analogue signal is above the "Set point".
- Remove the trigger when the analogue signal is below the "Reset point".
Trig when low
- Trigger when the analogue signal is below the "Set point".
- Remove the trigger when the analogue signal is above the "Reset point".
Note: The "Set point" value must be smaller than the "Reset point".
Outside set/reset point
- Trigger when the analogue signal is above the "Set point" or below the "Reset point".
- Remove the trigger when the analogue signal is between the "Set point" and the "Reset
point".
Between set/reset pts
- Trigger when the analogue signal is between the "Set point" and the "Reset point".
- Remove the trigger when the analogue signal is above the "Set point" or below the
"Reset point".
Yes
Will ask for a suffix to add to the voice message after speaking the analogue sensor
value. This would normally be the relevant engineering unit. If this is "Yes" the next
setting will prompt for the suffix voice message to be recorded.
*No (default)
Will speak the analogue value with no suffix.
Date: 31/10/12
Page 30File: 700b Technical Manual ver1.9.3.docm