EDAC Electronics Ltd. EDAC700 RTU Technical Reference Manual page 26

Table of Contents

Advertisement

20mA Loop
4mA to 20mA analogue input.
10V Analogue
0V to 10V DC analogue input.
1V analogue
0V to 1V DC analogue input.
Output reset off
Digital output set OFF when EDAC700 RTU is powered up or reset.
Output reset on
Digital output set ON when EDAC700 RTU is powered up or reset.
Pulse accumulator
Please contact EDAC Electronics, New Zealand for information on this optional
expansion module.
Runtime meter
Please contact EDAC Electronics, New Zealand for information on this optional
expansion module.
If you are editing an entry with an Analogue Input Function, then extra analogue settings
will be presented. Proceed through the section
Analogue Settings
for details on these.
If you have completed that section, or you are editing an entry with any other Input
Function, the settings continue as follows.
The next setting is the Input Alarm method, which has the currently selected option
showing.
Scroll through the menu options using <Up> & <Down> to choose an appropriate alarm
method, which will be one of the following:
Latched input
Alarm Trigger will be latched on. If the sensor goes back into range the alarm trigger
will remain present until acknowledged by a user.
do not latch (default)
The alarm trigger will be removed if the sensor goes back into range. This means the
alarm is self-cancelling.
Date: 31/10/12
Page 26File: 700b Technical Manual ver1.9.3.docm