Power System Data 2; Functional Description; Setting Notes; Settings - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

2 Functions
2.5

Power System Data 2

The general protection data (P.System Data 2) include settings associated with all
functions rather than a specific protection or monitoring function. Parameter settings
P.System Data 2 can be switched using the setting group.
2.5.1

Functional Description

Setting Groups
In the 7UM61 relay, two independent setting groups (A and B) are possible. Whereas
setting values may vary, the selected functions of each setting group remain the same.
2.5.2

Setting Notes

To enter these group-specific general protection data (P.System Data 2), select in
General
the SETTINGS menu theGroup A (Parameter group A), and in it P.System Data
2. The other setting group is accessible under Group B.
At addresses 1101 U PRIMARY OP. and 1102 I PRIMARY OP., the primary refer-
Rated Values of the
System
ence voltage and reference current of the protected motor is entered. These values
are important for pickup settings. The allow the device to calculate operational values
as percentage values. For example, if a CT ratio of 500/1 is selected and the rated
current of the generator is 483 A, a value of 500 A should be entered at address 211
and a value of 483 A under I PRIMARY OP.. 483 amps are now displayed as 100%
in the percentage metering display.
Address 1108 ACTIVE POWER is used to specify the active power direction in the
Active Power Direc-
tion
normal mode (Generator = output or Motor = input) or to adapt it to the power
system conditions without device recabling.
2.5.3

Settings

Addr.
Parameter
1101
U PRIMARY OP.
1102
I PRIMARY OP.
1108
ACTIVE POWER
2.5.4

Information List

No.
Information
501
Relay PICKUP
511
Relay TRIP
533
IL1:
40
Setting Options
0.10 .. 400.00 kV
10 .. 50000 A
Generator
Motor
Type of In-
formation
AM
Relay PICKUP
AM
Relay GENERAL TRIP command
AM
Primary fault current IL1
Default Setting
6.30 kV
Primary Operating Voltage
483 A
Primary Operating Current
Generator
Measurement of Active Power for
Comments
Comments
7UM61 Manual
C53000-G1176-C127-3