3 Mounting and Commissioning
Table 3-8
1)
2)
3)
Jumpers X71, X72 and X73 on the C–I/O–1 board serve to set the bus address. The
jumpers must not be changed. The following table lists the jumper presettings.
The installation locations of the boards are shown in Figures 3-1 to 3-2 .
Table 3-9
246
Jumper setting of control voltages of binary inputs BI1 to BI8 on Input/Output
module module C– I/O–1 in the 7UM612
Binary Inputs
Jumper
BI8
X21/X22
BI9
X23/X24
BI10
X25/X26
BI11
X27/X28
BI12
X29/X30
BI13
X31/X32
BI14
X33/X34
BI15
X35/X36
Factory settings for devices with rated power supply voltages 24 VDC to 125 VDC
Factory settings for devices with rated power supply voltages 110 VDC to 220 VDC and
115/230 VAC
Use only with control voltages 220 VDC or 250 VDC
Module address jumper setting of input/output module C-I/O-1 for 7UM612
Jumper
Factory Setting
X71
L
X72
H
X73
H
1)
19 V Threshold
88 V Threshold
L
M
L
M
L
M
L
M
L
M
L
M
L
M
L
M
2)
3)
176 V Threshold
H
H
H
H
H
H
H
H
7UM61 Manual
C53000-G1176-C127-3