Siemens Siprotec 7UM611 Manual page 382

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
1702
I2>
1703
T WARN
1704
FACTOR K
1705
T COOL DOWN
1706
I2>>
1707
T I2>>
3001
UNDEREXCIT.
3002
1/xd CHAR. 1
3003
ANGLE 1
3004
T CHAR. 1
3005
1/xd CHAR. 2
3006
ANGLE 2
3007
T CHAR. 2
3008
1/xd CHAR. 3
3009
ANGLE 3
3010
T CHAR 3
3011
T SHRT Uex<
3014A
Umin
3101
REVERSE POWER
3102
P> REVERSE
3103
T-SV-OPEN
3104
T-SV-CLOSED
3105A
T-HOLD
3201
FORWARD POWER
3202
Pf<
3203
T-Pf<
3204
Pf>
3205
T-Pf>
3206A
MEAS. METHOD
3301
IMPEDANCE PROT.
3302
IMP I>
3303
U< SEAL-IN
3304
U<
3305
T-SEAL-IN
3306
ZONE Z1
3307
T-Z1
3308
ZONE Z1B
382
Function
C
Setting Options
Unbalance Load
3.0 .. 30.0 %
0.00 .. 60.00 sec; ∞
Unbalance Load
2.0 .. 100.0 sec; ∞
Unbalance Load
Unbalance Load
0 .. 50000 sec
Unbalance Load
10 .. 100 %
0.00 .. 60.00 sec; ∞
Unbalance Load
Underexcitation
OFF
ON
Block relay
Underexcitation
0.25 .. 3.00
50 .. 120 °
Underexcitation
0.00 .. 60.00 sec; ∞
Underexcitation
Underexcitation
0.25 .. 3.00
50 .. 120 °
Underexcitation
0.00 .. 60.00 sec; ∞
Underexcitation
Underexcitation
0.25 .. 3.00
50 .. 120 °
Underexcitation
0.00 .. 60.00 sec; ∞
Underexcitation
0.00 .. 60.00 sec; ∞
Underexcitation
Underexcitation
10.0 .. 125.0 V
Reverse Power
OFF
ON
Block relay
Reverse Power
-30.00 .. -0.50 %
0.00 .. 60.00 sec; ∞
Reverse Power
0.00 .. 60.00 sec; ∞
Reverse Power
0.00 .. 60.00 sec; ∞
Reverse Power
Forward Power
OFF
ON
Block relay
Forward Power
0.5 .. 120.0 %
0.00 .. 60.00 sec; ∞
Forward Power
Forward Power
1.0 .. 120.0 %
0.00 .. 60.00 sec; ∞
Forward Power
Forward Power
accurate
fast
Impedance
OFF
ON
Block relay
Impedance
1A
0.10 .. 20.00 A
5A
0.50 .. 100.00 A
Impedance
ON
OFF
Impedance
10.0 .. 125.0 V
Impedance
0.10 .. 60.00 sec
0.05 .. 130.00 Ω
Impedance
1A
0.01 .. 26.00 Ω
5A
0.00 .. 60.00 sec; ∞
Impedance
0.05 .. 65.00 Ω
Impedance
1A
0.01 .. 13.00 Ω
5A
Default Setting
10.6 %
Continously Permissible Current
I2
20.00 sec
Warning Stage Time Delay
18.7 sec
Negativ Sequence Factor K
1650 sec
Time for Cooling Down
60 %
I2>> Pickup
3.00 sec
T I2>> Time Delay
OFF
Underexcitation Protection
0.41
Conductance Intersect Charac-
teristic 1
80 °
Inclination Angle of Characteris-
tic 1
10.00 sec
Characteristic 1 Time Delay
0.36
Conductance Intersect Charac-
teristic 2
90 °
Inclination Angle of Characteris-
tic 2
10.00 sec
Characteristic 2 Time Delay
1.10
Conductance Intersect Charac-
teristic 3
90 °
Inclination Angle of Characteris-
tic 3
0.30 sec
Characteristic 3 Time Delay
0.50 sec
T-Short Time Delay (Char. &
Uexc<)
25.0 V
Undervoltage blocking Pickup
OFF
Reverse Power Protection
-1.93 %
P> Reverse Pickup
10.00 sec
Time Delay Long (without Stop
Valve)
1.00 sec
Time Delay Short (with Stop
Valve)
0.00 sec
Pickup Holding Time
OFF
Forward Power Supervision
9.7 %
P-forw.< Supervision Pickup
10.00 sec
T-P-forw.< Time Delay
96.6 %
P-forw.> Supervision Pickup
10.00 sec
T-P-forw.> Time Delay
accurate
Method of Operation
OFF
Impedance Protection
1.35 A
Fault Detection I> Pickup
6.75 A
OFF
State of Undervoltage Seal-in
80.0 V
Undervoltage Seal-in Pickup
4.00 sec
Duration of Undervoltage Seal-in
2.90 Ω
Impedance Zone Z1
0.58 Ω
0.10 sec
Impedance Zone Z1 Time Delay
4.95 Ω
Impedance Zone Z1B
0.99 Ω
C53000-G1176-C127-3