Information List - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

Addr.
Parameter
1608
TEMP. SCAL.
1609
TEMP. SCAL.
1610A
I ALARM
1612A
Kτ-FACTOR
1615A
I MAX THERM.
1616A
T EMERGENCY
2.9.4

Information List

No.
Information
1503
>BLK ThOverload
1506
>RM th.rep. O/L
1507
>Emer.Start O/L
1508
>Fail.Temp.inp
1511
Th.Overload OFF
1512
Th.Overload BLK
1513
Overload ACT
1514
Fail.Temp.inp
1515
O/L I Alarm
O/L Θ Alarm
1516
1517
O/L Th. pick.up
1519
RM th.rep. O/L
1521
ThOverload TRIP
7UM61 Manual
C53000-G1176-C127-3
C
Setting Options
40 .. 300 °C
104 .. 572 °F
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
1.0 .. 10.0
1A
0.50 .. 8.00 A
5A
2.50 .. 40.00 A
10 .. 15000 sec
Type of In-
formation
EM
>BLOCK thermal overload protection
EM
>Reset memory for thermal replica O/L
EM
>Emergency start O/L
EM
>Failure temperature input
AM
Thermal Overload Protection OFF
AM
Thermal Overload Protection BLOCKED
AM
Overload Protection ACTIVE
AM
Failure temperature input
AM
Overload Current Alarm (I alarm)
AM
Thermal Overload Alarm
AM
Thermal Overload picked up
AM
Reset memory for thermal replica O/L
AM
Thermal Overload TRIP
2.9 Thermal Overload Protection (ANSI 49)
Default Setting
100 °C
Temperature for Scaling
212 °F
Temperature for Scaling
1.00 A
Current Overload Alarm
Setpoint
5.00 A
1.0
Kt-Factor when Motor
Stops
3.30 A
Maximum Current for
Thermal Replica
16.50 A
100 sec
Emergency Time
Comments
Comments
69