Siemens Siprotec 7UM611 Manual page 385

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

Addr.
Parameter
5106
IEE<
5201
SEF 3rd HARM.
5202
U0 3.HARM<
5203
U0 3.HARM>
5204
T SEF 3. HARM.
5205
P min >
5206
U1 min >
6501
STARTUP MOTOR
6502
START. CURRENT
6503
STARTING TIME
6504
LOCK ROTOR TIME
6505
I MOTOR START
6601
RESTART INHIBIT
6602
IStart/IMOTnom
6603
T START MAX
6604
T EQUAL
6606
MAX.WARM STARTS
6607
#COLD-#WARM
6608
Kτ at STOP
6609
Kτ at RUNNING
6610
T MIN. INHIBIT
7001
BREAKER FAILURE
7002
TRIP INTERN
7003
CIRC. BR. I>
7004
TRIP-Timer
7101
INADVERT. EN.
7102
I STAGE
7103
RELEASE U1<
7104
PICK UP T U1<
7105
DROP OUT T U1<
7110
FltDisp.LED/LCD
8001
FUSE FAIL MON.
8101
MEASURE. SUPERV
8102
BALANCE U-LIMIT
8103
BAL. FACTOR U
7UM61 Manual
C53000-G1176-C127-3
Function
C
Setting Options
Sens. E Fault
1.5 .. 50.0 mA; 0
SEF 3.Harm.
OFF
ON
Block relay
SEF 3.Harm.
0.2 .. 40.0 V
SEF 3.Harm.
0.2 .. 40.0 V
0.00 .. 60.00 sec; ∞
SEF 3.Harm.
SEF 3.Harm.
10 .. 100 %; 0
SEF 3.Harm.
50.0 .. 125.0 V; 0
Start Motor
OFF
ON
Block relay
Start Motor
1A
0.10 .. 16.00 A
5A
0.50 .. 80.00 A
Start Motor
1.0 .. 180.0 sec
0.5 .. 120.0 sec; ∞
Start Motor
Start Motor
1A
0.60 .. 10.00 A
5A
3.00 .. 50.00 A
Restart Motor
OFF
ON
Block relay
Restart Motor
1.5 .. 10.0
Restart Motor
3.0 .. 320.0 sec
Restart Motor
0.0 .. 320.0 min
Restart Motor
1 .. 4
Restart Motor
1 .. 2
Restart Motor
1.0 .. 100.0
Restart Motor
1.0 .. 100.0
Restart Motor
0.2 .. 120.0 min
Breaker Failure
OFF
ON
Block relay
Breaker Failure
OFF
BO3
CFC
Breaker Failure
1A
0.04 .. 2.00 A
5A
0.20 .. 10.00 A
0.06 .. 60.00 sec; ∞
Breaker Failure
Inadvert. En.
OFF
ON
Block relay
0.1 .. 20.0 A; ∞
Inadvert. En.
1A
0.5 .. 100.0 A; ∞
5A
Inadvert. En.
10.0 .. 125.0 V; 0
0.00 .. 60.00 sec; ∞
Inadvert. En.
0.00 .. 60.00 sec; ∞
Inadvert. En.
Device
Target on PU
Target on TRIP
Measurem.Superv
OFF
ON
Measurem.Superv
OFF
ON
Measurem.Superv
10 .. 100 V
Measurem.Superv
0.58 .. 0.90
Default Setting
0.0 mA
Iee< Pickup (Interrupted Circuit)
OFF
Stator Earth Fault Protection
3rdHarm.
1.0 V
U0 3rd Harmonic< Pickup
2.0 V
U0 3rd Harmonic> Pickup
0.50 sec
T SEF 3rd Harmonic Time Delay
40 %
Release Threshold Pmin>
80.0 V
Release Threshold U1min>
OFF
Motor Starting Time Supervision
3.12 A
Starting Current of Motor
15.60 A
8.5 sec
Starting Time of Motor
6.0 sec
Permissible Locked Rotor Time
1.60 A
Current Pickup Value of Motor
Starting
8.00 A
OFF
Restart Inhibit for Motors
4.9
I Start / I Motor nominal
8.5 sec
Maximum Permissible Starting
Time
1.0 min
Temperature Equalization Time
2
Permissible Number of Warm
Starts
1
Number of Cold Starts - Warm
Starts
5.0
Extension of Time Constant at
Stop
2.0
Extension of Time Constant at
Running
6.0 min
Minimum Restart Inhibit Time
OFF
Breaker Failure Protection
OFF
Start with Internal TRIP
Command
0.20 A
Supervision Current Pickup
1.00 A
0.25 sec
TRIP-Timer
OFF
Inadvertent Energisation
0.3 A
I Stage Pickup
1.5 A
50.0 V
Release Threshold U1<
5.00 sec
Pickup Time Delay T U1<
1.00 sec
Drop Out Time Delay T U1<
Target on PU
Fault Display on LED / LCD
OFF
Fuse Failure Monitor
OFF
Measurement Supervision
50 V
Voltage Threshold for Balance
Monitoring
0.75
Balance Factor for Voltage
Monitor
A.7 Settings
Comments
385