2 Functions
Addr.
Parameter
405
POST REC. TIME
406
BinIn CAPT.TIME

2.35.4.4 Information List

No.
Information
-
FltRecSta
4
>Trig.Wave.Cap.
203
Wave. deleted

2.35.5 Date and Time Stamping

The integrated date/time management allows exact time-specific allocation of events,
for example in the operational and fault indications or the minimum/maximum value
lists.

2.35.5.1 Functional Description

Mode of Operation
The time can be influenced by
• external synchronisation sources (DCF77, IRIG B, SyncBox, IEC 60 870–5–103),
• external minute pulses via binary input.
Note
On device delivery the internal clock RTC is always set by default as synchronisation
source, regardless of whether the device is equipped with a system interface or not. If
the time synchronisation is to use an external source, it must be selected.
The procedure for changing the synchronization source is explained in detail in the
SIPROTEC
218
Setting Options
0.05 .. 0.50 sec
0.10 .. 5.00 sec; ∞
Type of In-
formation
IE
EM
AM_W
internal RTC (Real Time Clock),
®
4 System Description.
No.
Operating Mode
1
Internal
2
IEC 60870-5-103
3
PROFIBUS DP
4
IRIG B Time signal
5
DCF77 Time signal
6
Sync. Box Time signal
7
Pulse via binary input
8
Field bus
Default Setting
0.10 sec
Captured Waveform after Event
0.50 sec
Capture Time via Binary Input
Comments
Fault Recording Start
>Trigger Waveform Capture
Waveform data deleted
Comments
Internal synchronization using RTC (default)
External synchronization using system interface (IEC
60 870–5–103)
External synchronization using PROFIBUS interface
External synchronization using IRIG B (telegram
format IRIG-B000)
External synchronization using DCF 77
External synchronization using SIMEAS Sync. Box
External synchronization with pulse via binary input
External synchronization using Modbus interface
Comments