The vector jump function becomes ineffective on exiting the admissible frequency
band. The same applies for the voltage. In such a case the limiting parameters are U
MIN and U MAX.
If the frequency or voltage range is not maintained, the logic generates a logical 1, and
the reset input is continuously active. The result of the vector jump measurement is
suppressed. If, for instance, the voltage is connected, and the frequency range is cor-
rect, the logical 1 changes to 0. The timer T BLOCK with reset delay keeps the reset
input active for a certain time, thus preventing a pickup caused by the vector jump
function.
If a short-circuit causes the voltage to drop abruptly to a low value, the reset input is
immediately activated to block the function. The vector jump function is thus prevented
from causing a trip.
Figure 2-40
Logic Diagram of the Vector Jump Detection

2.20.2 Setting Notes

The vector jump protection is only effective and available if address 146 VECTOR
General
JUMP is set to Enabled during configuration.
Address 4601 VECTOR JUMP serves to switch the function ON or OFF or to block only
the trip command (Block relay).
The value to be set for the vector jump (address 4602 DELTA PHI) depends on the
Pickup Values
feed and load conditions. Abrupt active power changes cause a jump of the voltage
7UM61 Manual
C53000-G1176-C127-3
2.20 Jump of Voltage Vector