Siemens Siprotec 7UM611 Manual page 198

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

2 Functions
Addr.
Parameter
9092A
RTD 9 LOCATION
9093
RTD 9 STAGE 1
9094
RTD 9 STAGE 1
9095
RTD 9 STAGE 2
9096
RTD 9 STAGE 2
9101A
RTD10 TYPE
9102A
RTD10 LOCATION
9103
RTD10 STAGE 1
9104
RTD10 STAGE 1
9105
RTD10 STAGE 2
9106
RTD10 STAGE 2
9111A
RTD11 TYPE
9112A
RTD11 LOCATION
9113
RTD11 STAGE 1
9114
RTD11 STAGE 1
9115
RTD11 STAGE 2
9116
RTD11 STAGE 2
198
Setting Options
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Default Setting
Other
RTD 9: Location
100 °C
RTD 9: Temperature Stage 1
Pickup
212 °F
RTD 9: Temperature Stage 1
Pickup
120 °C
RTD 9: Temperature Stage 2
Pickup
248 °F
RTD 9: Temperature Stage 2
Pickup
Not connected
RTD10: Type
Other
RTD10: Location
100 °C
RTD10: Temperature Stage 1
Pickup
212 °F
RTD10: Temperature Stage 1
Pickup
120 °C
RTD10: Temperature Stage 2
Pickup
248 °F
RTD10: Temperature Stage 2
Pickup
Not connected
RTD11: Type
Other
RTD11: Location
100 °C
RTD11: Temperature Stage 1
Pickup
212 °F
RTD11: Temperature Stage 1
Pickup
120 °C
RTD11: Temperature Stage 2
Pickup
248 °F
RTD11: Temperature Stage 2
Pickup
Comments