Information List - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

2 Functions
Addr.
Parameter
1706
I2>>
1707
T I2>>

2.10.4 Information List

No.
Information
5143
>BLOCK I2
5146
>RM th.rep. I2
5151
I2 OFF
5152
I2 BLOCKED
5153
I2 ACTIVE
5156
I2> Warn
5158
RM th.rep. I2
5159
I2>> picked up
5160
I2>> TRIP
I2 Θ TRIP
5161
5165
I2> picked up
76
Setting Options
10 .. 100 %
0.00 .. 60.00 sec; ∞
Type of In-
formation
EM
>BLOCK I2 (Unbalance Load)
EM
>Reset memory for thermal replica I2
AM
I2 switched OFF
AM
I2 is BLOCKED
AM
I2 is ACTIVE
AM
Unbalanced load: Current warning stage
AM
Reset memory of thermal replica I2
AM
I2>> picked up
AM
Unbalanced load: TRIP of current stage
AM
Unbalanced load: TRIP of thermal stage
AM
I2> picked up
Default Setting
60 %
I2>> Pickup
3.00 sec
T I2>> Time Delay
Comments
Comments
7UM61 Manual
C53000-G1176-C127-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7um612

Table of Contents