Parameter
9072A
RTD 7 LOCATION
9073
RTD 7 STAGE 1
9074
RTD 7 STAGE 1
9075
RTD 7 STAGE 2
9076
RTD 7 STAGE 2
9081A
RTD 8 TYPE
9082A
RTD 8 LOCATION
9083
RTD 8 STAGE 1
9084
RTD 8 STAGE 1
9085
RTD 8 STAGE 2
9086
RTD 8 STAGE 2
9091A
RTD 9 TYPE
9092A
RTD 9 LOCATION
9093
RTD 9 STAGE 1
9094
RTD 9 STAGE 1
9095
RTD 9 STAGE 2
9096
RTD 9 STAGE 2
9101A
RTD10 TYPE
9102A
RTD10 LOCATION
9103
RTD10 STAGE 1
9104
RTD10 STAGE 1
9105
RTD10 STAGE 2
9106
RTD10 STAGE 2
9111A
RTD11 TYPE
7UM61 Manual
C53000-G1176-C127-3
Function
C
Setting Options
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Default Setting
Other
RTD 7: Location
100 °C
RTD 7: Temperature Stage 1
Pickup
212 °F
RTD 7: Temperature Stage 1
Pickup
120 °C
RTD 7: Temperature Stage 2
Pickup
248 °F
RTD 7: Temperature Stage 2
Pickup
Not connected
RTD 8: Type
Other
RTD 8: Location
100 °C
RTD 8: Temperature Stage 1
Pickup
212 °F
RTD 8: Temperature Stage 1
Pickup
120 °C
RTD 8: Temperature Stage 2
Pickup
248 °F
RTD 8: Temperature Stage 2
Pickup
Not connected
RTD 9: Type
Other
RTD 9: Location
100 °C
RTD 9: Temperature Stage 1
Pickup
212 °F
RTD 9: Temperature Stage 1
Pickup
120 °C
RTD 9: Temperature Stage 2
Pickup
248 °F
RTD 9: Temperature Stage 2
Pickup
Not connected
RTD10: Type
Other
RTD10: Location
100 °C
RTD10: Temperature Stage 1
Pickup
212 °F
RTD10: Temperature Stage 1
Pickup
120 °C
RTD10: Temperature Stage 2
Pickup
248 °F
RTD10: Temperature Stage 2
Pickup
Not connected
RTD11: Type