2 Functions
The following figure shows the logic diagram for the restart inhibit.
Figure 2-54

2.25.2 Setting Notes

Restart inhibit is only effective and available if address 166 RESTART INHIBIT was
General
set to Enabled during configuration. If the function is not required Disabled is set.
Address 6601RESTART INHIBIT serves to switch the function ON or OFF or to block
only the trip command (Block relay).
152
Logic diagram of the Restart Inhibit
7UM61 Manual
C53000-G1176-C127-3