Change Group; Setting Notes; Settings; Information List - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

2.4

Change Group

operation the user can locally switch between setting groups using the operator panel,
binary inputs (if so configured), the operator and service interface per PC, or via the
system interface.
A setting group includes the setting values for all functions that have been selected as
Enabled during configuration (see Section 2.2). In the 7UM61 device, two indepen-
dent setting groups (A and B) are available. Whereas setting values may vary, the se-
lected functions of each setting group remain the same.
Where different settings are required for operational reasons, e.g. in pumped storage
power stations with a machine operating alternately as a generator and a motor, these
settings are made in the setting groups and stored in the device. Depending on the
operating mode, the applicable setting group is activated, usually via a binary input.
If multiple setting groups are not required, Group A is the default selection. The rest of
this section is not relevant.
2.4.1

Setting Notes

General
If the changeover option is desired, on function extent configuration group changeover
must be set to Grp Chge OPTION = Enabled (address 103). When setting the func-
tion parameters, you configure first setting group A, then setting group B. How to
proceed and how to copy or reset settings groups are described in the SIPROTEC
System Description /1/.
How to switch between setting groups externally using binary inputs is described in the
Mounting and Commissioning section.
2.4.2

Settings

Addr.
Parameter
302
CHANGE
2.4.3

Information List

No.
Information
-
Group A
-
Group B
7
>Set Group Bit0
8
>Set Group Bit1
7UM61 Manual
C53000-G1176-C127-3
Two independent groups of parameters can be set for the device functions. During
Setting Options
Group A
Group B
Binary Input
Protocol
Type of In-
formation
IE
IE
EM
EM
Default Setting
Group A
Change to Another Setting Group
Comments
Group A
Group B
>Setting Group Select Bit 0
>Setting Group Select Bit 1
2.4 Change Group
®
Comments
39