Information List - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

2 Functions
Addr.
Parameter
4517
df4/dt & f4
4518
U MIN
4519A
df1/2 HYSTERES.
4520A
df1/2 M-WINDOW
4521A
df3/4 HYSTERES.
4522A
df3/4 M-WINDOW

2.19.4 Information List

No.
Information
5503
>df/dt block
5504
>df1/dt block
5505
>df2/dt block
5506
>df3/dt block
5507
>df4/dt block
5511
df/dt OFF
5512
df/dt BLOCKED
5513
df/dt ACTIVE
5514
df/dt U< block
5516
df1/dt pickup
5517
df2/dt pickup
5518
df3/dt pickup
5519
df4/dt pickup
5520
df1/dt TRIP
5521
df2/dt TRIP
5522
df3/dt TRIP
5523
df4/dt TRIP
122
Setting Options
OFF
ON
10.0 .. 125.0 V; 0
0.02 .. 0.99 Hz/s
1 .. 25 Cycle
0.02 .. 0.99 Hz/s
1 .. 25 Cycle
Type of In-
formation
EM
>BLOCK Rate-of-frequency-change prot.
EM
>BLOCK df1/dt stage
EM
>BLOCK df2/dt stage
EM
>BLOCK df3/dt stage
EM
>BLOCK df4/dt stage
AM
df/dt is switched OFF
AM
df/dt is BLOCKED
AM
df/dt is ACTIVE
AM
df/dt is blocked by undervoltage
AM
Stage df1/dt picked up
AM
Stage df2/dt picked up
AM
Stage df3/dt picked up
AM
Stage df4/dt picked up
AM
Stage df1/dt TRIP
AM
Stage df2/dt TRIP
AM
Stage df3/dt TRIP
AM
Stage df4/dt TRIP
Default Setting
OFF
AND logic with pickup of stage f4
65.0 V
Minimum Operating Voltage Umin
0.10 Hz/s
Reset Hysteresis for df1/dt &
df2/dt
5 Cycle
Measuring Window for df1/dt &
df2/dt
0.40 Hz/s
Reset Hysteresis for df3/dt &
df4/dt
5 Cycle
Measuring Window for df3/dt &
df4/dt
Comments
Comments
7UM61 Manual
C53000-G1176-C127-3