Information List; Set Points (Measured Values); Functional Description - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

2.35.2.2 Information List

No.
Information
601
IL1 =
602
IL2 =
603
IL3 =
605
I1 =
606
I2 =
621
UL1E=
622
UL2E=
623
UL3E=
624
UL12=
625
UL23=
626
UL31=
627
UE =
629
U1 =
630
U2 =
641
P =
642
Q =
644
Freq=
645
S =
650
UE3h=
765
U/f =
830
IEE =
831
3I0 =
832
U0 =
901
PF =
902
PHI =
903
R =
904
X =

2.35.3 Set Points (Measured Values)

2.35.3.1 Functional Description

Limit Value Moni-
SIPROTEC
torings
be set. If during operation a value transgresses one of these limits, the device gener-
ates an alarm which is displayed as an operational indication. As for all operational in-
dications, it is possible to output the information to LED and/or output relay and via in-
terfaces. In contrast to the actual protective functions, such as time-overcurrent
protection or overload protection, this monitoring program runs in the background and
may not respond promptly during a fault if the measured values change rapidly and
protective functions pick up. Moreover, since an indication is not generated until the
set limit value has been transgressed several times, these monitoring functions cannot
respond immediately before a protection trip.
With the 7UM61, only the limit value of the undercurrent protection IL< is configured
when the device is delivered from the factory. Further limit values can be configured if
7UM61 Manual
C53000-G1176-C127-3
Type of In-
formation
MW
I L1
MW
I L2
MW
I L3
MW
I1 (positive sequence)
MW
I2 (negative sequence)
MW
U L1-E
MW
U L2-E
MW
U L3-E
MW
U L12
MW
U L23
MW
U L31
MW
Displacement voltage UE
MW
U1 (positive sequence)
MW
U2 (negative sequence)
MW
P (active power)
MW
Q (reactive power)
MW
Frequency
MW
S (apparent power)
MW
UE 3rd harmonic
MW
(U/Un) / (f/fn)
MW
Senstive Earth Fault Current
MW
3I0 (zero sequence)
MW
U0 (zero sequence)
MW
Power Factor
MW
Power angle
MW
Resistance
MW
Reactance
®
7UM61 allows limit levels for important measured and counter values to