2 Functions
Addr.
Parameter
4209
f3 PICKUP
4210
T f3
4211
f4 PICKUP
4212
f4 PICKUP
4213
T f4
4214
THRESHOLD f4
4215
Umin

2.17.4 Information List

No.
Information
5203
>BLOCK Freq.
5206
>BLOCK f1
5207
>BLOCK f2
5208
>BLOCK f3
5209
>BLOCK f4
5211
Freq. OFF
5212
Freq. BLOCKED
5213
Freq. ACTIVE
5214
Freq UnderV Blk
5232
f1 picked up
5233
f2 picked up
5234
f3 picked up
5235
f4 picked up
5236
f1 TRIP
5237
f2 TRIP
5238
f3 TRIP
5239
f4 TRIP
112
Setting Options
40.00 .. 65.00 Hz
0.00 .. 100.00 sec
40.00 .. 65.00 Hz
40.00 .. 65.00 Hz
0.00 .. 100.00 sec
automatic
f>
f<
10.0 .. 125.0 V; 0
Type of In-
formation
EM
>BLOCK frequency protection
EM
>BLOCK stage f1
EM
>BLOCK stage f2
EM
>BLOCK stage f3
EM
>BLOCK stage f4
AM
Frequency protection is OFF
AM
Frequency protection is BLOCKED
AM
Frequency protection is ACTIVE
AM
Frequency protection undervoltage Blk
AM
f1 picked up
AM
f2 picked up
AM
f3 picked up
AM
f4 picked up
AM
f1 TRIP
AM
f2 TRIP
AM
f3 TRIP
AM
f4 TRIP
Default Setting
59.50 Hz
f3 Pickup
20.00 sec
T f3 Time Delay
52.00 Hz
f4 Pickup
62.00 Hz
f4 Pickup
10.00 sec
T f4 Time Delay
automatic
Handling of Threshold Stage f4
65.0 V
Minimum Required Voltage for
Operation
Comments
Comments
7UM61 Manual
C53000-G1176-C127-3