A Appendix
Addr.
Parameter
4314
T COOL DOWN
4501
df/dt Protect.
4502
df1/dt >/<
4503
STAGE df1/dt
4504
T df1/dt
4505
df1/dt & f1
4506
df2/dt >/<
4507
STAGE df2/dt
4508
T df2/dt
4509
df2/dt & f2
4510
df3/dt >/<
4511
STAGE df3/dt
4512
T df3/dt
4513
df3/dt & f3
4514
df4/dt >/<
4515
STAGE df4/dt
4516
T df4/dt
4517
df4/dt & f4
4518
U MIN
4519A
df1/2 HYSTERES.
4520A
df1/2 M-WINDOW
4521A
df3/4 HYSTERES.
4522A
df3/4 M-WINDOW
4601
VECTOR JUMP
4602
DELTA PHI
4603
T DELTA PHI
4604
T RESET
4605A
U MIN
4606A
U MAX
4607A
T BLOCK
5001
S/E/F PROT.
5002
U0>
5003
3I0>
5004
DIR. ANGLE
5005
T S/E/F
5101
O/C PROT. Iee>
5102
IEE>
5103
T IEE>
5104
IEE>>
5105
T IEE>>
384
Function
C
Setting Options
Overexcitation
0 .. 20000 sec
df/dt Protect.
OFF
ON
Block relay
df/dt Protect.
-df/dt<
+df/dt>
0.1 .. 10.0 Hz/s; ∞
df/dt Protect.
0.00 .. 60.00 sec; ∞
df/dt Protect.
df/dt Protect.
OFF
ON
df/dt Protect.
-df/dt<
+df/dt>
0.1 .. 10.0 Hz/s; ∞
df/dt Protect.
0.00 .. 60.00 sec; ∞
df/dt Protect.
df/dt Protect.
OFF
ON
df/dt Protect.
-df/dt<
+df/dt>
0.1 .. 10.0 Hz/s; ∞
df/dt Protect.
0.00 .. 60.00 sec; ∞
df/dt Protect.
df/dt Protect.
OFF
ON
df/dt Protect.
-df/dt<
+df/dt>
0.1 .. 10.0 Hz/s; ∞
df/dt Protect.
0.00 .. 60.00 sec; ∞
df/dt Protect.
df/dt Protect.
OFF
ON
df/dt Protect.
10.0 .. 125.0 V; 0
df/dt Protect.
0.02 .. 0.99 Hz/s
df/dt Protect.
1 .. 25 Cycle
df/dt Protect.
0.02 .. 0.99 Hz/s
df/dt Protect.
1 .. 25 Cycle
Vector Jump
OFF
ON
Block relay
2 .. 30 °
Vector Jump
0.00 .. 60.00 sec; ∞
Vector Jump
0.10 .. 60.00 sec; ∞
Vector Jump
Vector Jump
10.0 .. 125.0 V
Vector Jump
10.0 .. 170.0 V
0.00 .. 60.00 sec; ∞
Vector Jump
Stator E Fault
OFF
ON
Block relay
Stator E Fault
2.0 .. 125.0 V
Stator E Fault
2 .. 1000 mA
0 .. 360 °
Stator E Fault
0.00 .. 60.00 sec; ∞
Stator E Fault
Sens. E Fault
OFF
ON
Block relay
Sens. E Fault
2 .. 1000 mA
0.00 .. 60.00 sec; ∞
Sens. E Fault
Sens. E Fault
2 .. 1000 mA
0.00 .. 60.00 sec; ∞
Sens. E Fault
Default Setting
3600 sec
Time for Cooling Down
OFF
Rate-of-frequency-change pro-
tection
-df/dt<
Mode of Threshold (df1/dt >/<)
1.0 Hz/s
Pickup Value of df1/dt Stage
0.50 sec
Time Delay of df1/dt Stage
OFF
AND logic with pickup of stage f1
-df/dt<
Mode of Threshold (df2/dt >/<)
1.0 Hz/s
Pickup Value of df2/dt Stage
0.50 sec
Time Delay of df2/dt Stage
OFF
AND logic with pickup of stage f2
-df/dt<
Mode of Threshold (df3/dt >/<)
4.0 Hz/s
Pickup Value of df3/dt Stage
0.00 sec
Time Delay of df3/dt Stage
OFF
AND logic with pickup of stage f3
-df/dt<
Mode of Threshold (df4/dt >/<)
4.0 Hz/s
Pickup Value of df4/dt Stage
0.00 sec
Time Delay of df4/dt Stage
OFF
AND logic with pickup of stage f4
65.0 V
Minimum Operating Voltage
Umin
0.10 Hz/s
Reset Hysteresis for df1/dt &
df2/dt
5 Cycle
Measuring Window for df1/dt &
df2/dt
0.40 Hz/s
Reset Hysteresis for df3/dt &
df4/dt
5 Cycle
Measuring Window for df3/dt &
df4/dt
OFF
Jump of Voltage Vector
10 °
Jump of Phasor DELTA PHI
0.00 sec
T DELTA PHI Time Delay
5.00 sec
Reset Time after Trip
80.0 V
Minimal Operation Voltage U MIN
130.0 V
Maximal Operation Voltage U
MAX
0.10 sec
Time Delay of Blocking
OFF
Stator Earth Fault Protection
10.0 V
U0> Pickup
5 mA
3I0> Pickup
15 °
Angle for Direction Determination
0.30 sec
T S/E/F Time Delay
OFF
Sensitive Earth Current Protec-
tion
10 mA
Iee> Pickup
5.00 sec
T Iee> Time delay
23 mA
Iee>> Pickup
1.00 sec
T Iee>> Time Delay
C53000-G1176-C127-3