Siemens Siprotec 7UM611 Manual page 388

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
9032A
RTD 3 LOCATION
9033
RTD 3 STAGE 1
9034
RTD 3 STAGE 1
9035
RTD 3 STAGE 2
9036
RTD 3 STAGE 2
9041A
RTD 4 TYPE
9042A
RTD 4 LOCATION
9043
RTD 4 STAGE 1
9044
RTD 4 STAGE 1
9045
RTD 4 STAGE 2
9046
RTD 4 STAGE 2
9051A
RTD 5 TYPE
9052A
RTD 5 LOCATION
9053
RTD 5 STAGE 1
9054
RTD 5 STAGE 1
9055
RTD 5 STAGE 2
9056
RTD 5 STAGE 2
9061A
RTD 6 TYPE
9062A
RTD 6 LOCATION
9063
RTD 6 STAGE 1
9064
RTD 6 STAGE 1
9065
RTD 6 STAGE 2
9066
RTD 6 STAGE 2
9071A
RTD 7 TYPE
388
Function
C
Setting Options
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Default Setting
Other
RTD 3: Location
100 °C
RTD 3: Temperature Stage 1
Pickup
212 °F
RTD 3: Temperature Stage 1
Pickup
120 °C
RTD 3: Temperature Stage 2
Pickup
248 °F
RTD 3: Temperature Stage 2
Pickup
Not connected
RTD 4: Type
Other
RTD 4: Location
100 °C
RTD 4: Temperature Stage 1
Pickup
212 °F
RTD 4: Temperature Stage 1
Pickup
120 °C
RTD 4: Temperature Stage 2
Pickup
248 °F
RTD 4: Temperature Stage 2
Pickup
Not connected
RTD 5: Type
Other
RTD 5: Location
100 °C
RTD 5: Temperature Stage 1
Pickup
212 °F
RTD 5: Temperature Stage 1
Pickup
120 °C
RTD 5: Temperature Stage 2
Pickup
248 °F
RTD 5: Temperature Stage 2
Pickup
Not connected
RTD 6: Type
Other
RTD 6: Location
100 °C
RTD 6: Temperature Stage 1
Pickup
212 °F
RTD 6: Temperature Stage 1
Pickup
120 °C
RTD 6: Temperature Stage 2
Pickup
248 °F
RTD 6: Temperature Stage 2
Pickup
Not connected
RTD 7: Type
C53000-G1176-C127-3
Comments
7UM61 Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7um612

Table of Contents