3 Mounting and Commissioning
Table 3-4
Table 3-5
Table 3-6
1)
2)
244
Jumper setting for nominal voltage of the integrated power supply on the B–
CPU processor PCB for 7UM61.../CC
Jumper
60/110/125 VDC
X51
1–2
X52
1–2 and 3–4
X53
1–2
Jumper setting for the quiescent state of the life contact on the B–CPU proces-
sor PCB for 7UM61.../CC devices.
Jumper
Open in the quiescent
state
X40
1–2
Jumper settings for the control voltages of binary inputs BI1 through BI7 on the
B–CPU processor PCB for 7UM61.../CC
Binary Inputs
BI1
BI2
BI3
BI4
BI5
BI6
BI7
Factory settings for devices with rated power supply voltages 24 VDC to 125 VDC
Factory settings for devices with power supply voltages of 220 VDC to 250 VDC and 115/230
VAC
Rated voltage
220/250 VDC
115/230 VAC
2–3
2–3
2–3
Closed in the quiescent
state
2–3
Jumper
19 V Threshold
X21
L
X22
L
X23
L
X24
L
X25
L
X26
L
X27
L
24/48 VDC
1–2
none
none
Presetting
2–3
1)
2)
88 V Threshold
H
H
H
H
H
H
H