Use as Earth Short-
For low-voltage machines with incorporated neutral conductor or machines with low-
Circuit Protection
impedance earthed starpoint, the time-overcurrent protection of the phase branches
already is an earth short-circuit protection, since the short-circuit current also flows
through the faulty phase. If the sensitive earth current detection nevertheless is be
used as earth short-circuit protection, an external intermediate transformer must be
employed to ensure that the thermal limit values (15 A continuous, 100 A for <10 s,
300 A for <1 s) of this measuring input are not exceeded by the short-circuit current.

2.22.3 Settings

Addr.
Parameter
5101
O/C PROT. Iee>
5102
IEE>
5103
T IEE>
5104
IEE>>
5105
T IEE>>
5106
IEE<

2.22.4 Information List

No.
Information
1202
>BLOCK IEE>>
1203
>BLOCK IEE>
1221
IEE>> picked up
1223
IEE>> TRIP
1224
IEE> picked up
1226
IEE> TRIP
1231
>BLOCK Sens. E
1232
IEE OFF
1233
IEE BLOCKED
1234
IEE ACTIVE
5396
Fail. REF Iee<
7UM61 Manual
C53000-G1176-C127-3
2.22 Sensitive Earth Fault Protection (ANSI 51GN, 64R)
Setting Options
OFF
ON
Block relay
2 .. 1000 mA
0.00 .. 60.00 sec; ∞
2 .. 1000 mA
0.00 .. 60.00 sec; ∞
1.5 .. 50.0 mA; 0
Type of In-
formation
EM
>BLOCK IEE>>
EM
>BLOCK IEE>
AM
IEE>> picked up
AM
IEE>> TRIP
AM
IEE> picked up
AM
IEE> TRIP
EM
>BLOCK sensitiv earth current prot.
AM
Earth current prot. is swiched OFF
AM
Earth current prot. is BLOCKED
AM
Earth current prot. is ACTIVE
AM
Failure R/E/F protection Iee<
Default Setting
OFF
Sensitive Earth Current Protec-
tion
10 mA
Iee> Pickup
5.00 sec
T Iee> Time delay
23 mA
Iee>> Pickup
1.00 sec
T Iee>> Time Delay
0.0 mA
Iee< Pickup (Interrupted Circuit)
Comments
Comments
139