Direct Inputs And Outputs - GE N60 Instruction Manual

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

INPUTS/OUTPUTS
When the
command is received by the relay, two FlexLogic operands are created. These operands, which are stored
RESET
as events, reset the latches if the initiating condition has cleared. The three sources of
FlexLogic operand. Each individual source of a
RESET OP
,
(PUSHBUTTON)
RESET OP (COMMS)
selects the operand that creates the

5.9.6 Direct inputs and outputs

5.9.6.1 Direct inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INPUTS  DIRECT INPUT 1(64)
 DIRECT INPUT 1
These settings specify how the direct input information is processed.
5
DIRECT INPUT 1 NAME
DIRECT INPUT 1 DEVICE ID
identified here.
DIRECT INPUT 1 BIT NUMBER
identified as
DIRECT INPUT 1 BIT NUMBER
DIRECT INPUT 1 DEFAULT STATE
following choices are available:
On — Defaults the input to Logic 1
Off — Defaults the input to Logic 0
Latest/On — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 1. When communication resumes,
the input becomes fully operational.
Latest/Off — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 0. When communication resumes,
the input becomes fully operational.
5.9.6.2 Direct outputs
SETTINGS  INPUTS/OUTPUTS  DIRECT OUTPUTS  DIRECT OUTPUT 1(64)
 DIRECT OUTPUT 1
DIRECT OUT 1 NAME
DIR OUT 1 OPERAND
5-232
or
to identify the source of the command. The
RESET OP (OPERAND)
RESET OP (OPERAND)
DIRECT INPUT 1
NAME: Dir Ip 1
DIRECT INPUT 1
DEVICE ID: 1
DIRECT INPUT 1
BIT NUMBER: 1
DIRECT INPUT 1
DEFAULT STATE: Off
DIRECT INPUT 1
EVENTS: Disabled
— This setting allows the user to assign a descriptive name to the direct input.
— Represents the source of direct input 1. The specified direct input is driven by the device
— The bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
. This corresponds to the direct output number of the sending device.
— Represents the state of the direct input when the associated direct device is offline. The
DIRECT OUT 1 NAME:
Dir Out 1
DIRECT OUT 1 OPERAND:
Off
DIRECT OUTPUT 1
EVENTS: Disabled
— This setting allows the user to assign a descriptive name to the direct output.
— This sets the FlexLogic operand that determines the state of this direct output.
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
command also creates its individual operand
RESET
operand.
Range: up to 12 alphanumeric characters
Range: 1 to 16
Range: 1 to 64
Range: On, Off, Latest/On, Latest/Off
Range: Enabled, Disabled
Range: up to 12 alphanumeric characters
Range: FlexLogic operand
Range: Enabled, Disabled
CHAPTER 5: SETTINGS
commands each create the
RESET
RESET OP
setting here
RESET OPERAND

Advertisement

Table of Contents
loading

Table of Contents