CHAPTER 3: INSTALLATION
To activate the relay using EnerVista software:
1.
Navigate to Settings > Product Setup > Installation and change the Relay Settings field to "Programmed."
2.
Save the change.

3.6 Install software

3.6.1 EnerVista communication overview

The EnerVista UR Setup software communicates to the relay via the faceplate RS232 port or the rear panel RS485 /
Ethernet ports.
To communicate via the faceplate RS232 port, use a standard straight-through serial cable. Connect the DB-9 male end to
the relay and the DB-9 or DB-25 female end to the computer COM2 port as described in the CPU Communication Ports
section earlier in this chapter.
To communicate through the N60 rear RS485 port from a computer RS232 port, the GE Digital Energy RS232/RS485
converter box is required. This device (catalog number F485) connects to the computer using a straight-through serial
cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the N60 rear communications port. The
converter terminals (+, –, GND) are connected to the N60 communication module (+, –, COM) terminals. See the CPU
Communication Ports section in chapter 3 for details. The line is terminated with an R-C network (that is, 120 , 1 nF) as
described in this chapter.
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Figure 3-42: Relay communication options
INSTALL SOFTWARE
3
3-35