Settings File Traceability - GE N60 Instruction Manual

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

ENERVISTA SOFTWARE INTERFACE
2.
Enter the serial number of the N60 device to lock to the settings file in the Serial # Lock field.
3.
Click the OK button to apply the change.
4
The settings file and corresponding secure FlexLogic equations are now locked to the N60 device specified by the serial
number.

4.1.8 Settings file traceability

A traceability feature for settings files allows the user to quickly determine if the settings in a N60 device have been
changed since the time of installation from a settings file. When a settings file is transferred to a N60 device, the date, time,
and serial number of the N60 are sent back to EnerVista UR Setup and added to the settings file on the local computer. This
information can be compared with the N60 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the N60
device or obtained from the N60 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.
4-10
Figure 4-10: Settings file properties window
Figure 4-11: Settings file traceability
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES

Advertisement

Table of Contents
loading

Table of Contents