CHAPTER 5: SETTINGS
Lower the
VOLTAGE CUT-OFF LEVEL
valid measurements. Unless dictated otherwise by a specific application, the default settings of "0.02 pu" for
NOTE
CURRENT CUT-OFF LEVEL

5.3.3 Clear relay records

SETTINGS  PRODUCT SETUP  CLEAR RELAY RECORDS
 CLEAR RELAY
 RECORDS
Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-
programmable pushbuttons to clear specific records is a typical application for these commands. Since the N60 responds
to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-
programmable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-
programmable pushbuttons can provide extra security if required.
For example, to assign user-programmable pushbutton 1 to clear demand records, apply the following settings.
1.
Assign the clear demand function to pushbutton 1 by making the following change in the
 CLEAR RELAY RECORDS
: "
CLEAR DEMAND
PUSHBUTTON 1 ON
2.
Set the properties for user-programmable pushbutton 1 by making the following changes in the
SETUP  USER-PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1
PUSHBUTTON 1 FUNCTION
PUSHBTN 1 DROP-OUT TIME

5.3.4 Communications

5.3.4.1 Menu
SETTINGS  PRODUCT SETUP  COMMUNICATIONS
 COMMUNICATIONS
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
and
CURRENT CUT-OFF LEVEL
and "1.0 V" for
VOLTAGE CUT-OFF LEVEL
CLEAR EVENT RECORDS:
Off
CLEAR OSCILLOGRAPHY:
No
CLEAR DATA LOGGER:
Off
CLEAR DEMAND:
Off
CLEAR ENERGY:
Off
RESET UNAUTH ACCESS:
Off
CLEAR DIR I/O STATS:
Off
menu:
"
: "Self-reset"
: "0.20 s"
 SERIAL PORTS
 NETWORK
 ROUTING
with care as the relay accepts lower signals as
are recommended.
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Visible only for units with Direct I/O module
SETTINGS  PRODUCT SETUP
SETTINGS  PRODUCT
menu:
See below
See page 5-28
See page 5-33
PRODUCT SETUP
5
5-27