METERING

6.3.4 Synchrocheck

ACTUAL VALUES  METERING  SYNCHROCHECK  SYNCHROCHECK 1(2)
 SYNCHROCHECK 1
The actual values menu for synchrocheck 2 is identical to that of synchrocheck 1. If a synchrocheck function setting is
"Disabled," the corresponding actual values menu item does not display.

6.3.5 Tracking frequency

ACTUAL VALUES  METERING  TRACKING FREQUENCY
 TRACKING FREQUENCY
The tracking frequency displays here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE
System section of chapter 5 for details.

6.3.6 FlexElements

ACTUAL VALUES  METERING  FLEXELEMENTS  FLEXELEMENT 1(16)
 FLEXELEMENT 1
6
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6-2: FlexElement base units
Base unit
DCmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SENSITIVE DIR POWER
(Sns Dir Power)
SOURCE CURRENT
SOURCE ENERGY
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)
6-20
SYNCHROCHECK 1 DELTA
VOLT: 0.000 V
SYNCHROCHECK 1 DELTA
PHASE:
0.0°
SYNCHROCHECK 1 DELTA
FREQ: 0.00 Hz
TRACKING FREQUENCY
60.00 Hz
setting in the
SETTINGS  SYSTEM SETUP  POWER SYSTEM
FLEXELEMENT 1
OpSig: 0.000 pu
Description
BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
f
= 1 Hz
BASE
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
= maximum value of 3  V
P
BASE
for the sensitive power directional element(s).
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
 I
for the +IN and –IN inputs of the sources configured
BASE
BASE
 I
for the +IN and –IN inputs
BASE
CHAPTER 6: ACTUAL VALUES
menu. See the Power