CHAPTER 5: SETTINGS
0 disables Modbus over TCP/IP, meaning closes the Modbus TCP port. When the port number is changed to 0, the change
takes effect when the N60 is restarted. When it is set to 0, use the front panel or serial port to communicate with the relay.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
5.3.4.9 Protocol selection
The
menu setting allows selection of one of the following protocols: DNP 3.0, IEC60870-104, or IEC60870-103.
PROTOCOL
For any change to take effect, restart the unit.
The table shows which of DNP 3.0, IEC 60870-5-104, IEC 60870-5-103, and IEC 61850 protocols are operational on the
RS232, RS485, and Ethernet ports. It shows all possible combinations of the
Table 5-8: Port and protocol combinations
PROTOCOL
DNP CHANNEL 1(2) PORT
setting
settings
DNP
Channel 1: Eth TCP
Channel 2: Eth TCP
Channel 1: Eth TCP
Channel 2: none
Channel 1: none
Channel 2: Eth TCP
Channel 1: Eth UDP
Channel 2: none
Channel 1: Eth TCP
Channel 2: RS485
Channel 1: Eth TCP
Channel 2: RS232
Channel 1: Eth UDP
Channel 2: RS485
Channel 1: Eth UDP
Channel 2: RS232
Channel 1: RS485
Channel 2: Eth TCP
Channel 1: RS232
Channel 2: Eth TCP
Channel 1: RS485
Channel 2: RS232
Channel 1: RS232
Channel 2: RS485
Channel 1: RS485
Channel 2: none
IEC 104
IEC 103
5.3.4.10 DNP protocol
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL
 DNP PROTOCOL
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
RS232
RS485
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
DNP
DNP
Modbus
Modbus
DNP
DNP
Modbus
Modbus
DNP
DNP
Modbus
DNP
DNP
DNP
DNP
Modbus
DNP
Modbus
Modbus
Modbus
IEC 103
 DNP CHANNELS
DNP ADDRESS:
1
 DNP NETWORK
 CLIENT ADDRESSES
and
PROTOCOL
DNP CHANNEL 1(2) PORT
Ethernet
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
DNP, Modbus, IEC 61850
Modbus, IEC 61850
Modbus, IEC 61850
Modbus, IEC 61850
IEC 104, Modbus, IEC 61850
Modbus, IEC 61850
See below
Range: 0 to 65535 in steps of 1
See below
PRODUCT SETUP
settings.
5
5-37