PRODUCT SETUP
To configure Server authentication:
1.
In the EnerVista software, choose Device authentication and log in as Administrator.
2.
Configure the following RADIUS server parameters: IP address, authentication port, shared secret, and vendor ID.
3.
On the RADIUS server, configure the user accounts. Do not use the five pre-defined roles as user names (Administrator,
Supervisor, Engineer, Operator, Observer) in the RADIUS server. If you do, the UR relay automatically provides the
authentication from the device.
4.
In the EnerVista software, choose Server authentication and log in using the user name and password configured on
the RADIUS server for Server authentication login.
5.
After making any required changes, log out.
5
Pushbuttons (both user-control buttons and user-programmable buttons) located on the front panel can be pressed by an
Administrator or Engineer role. This also applies to the
displayed on the front panel or the Targets panel of the EnerVista software. The
allows these two roles to press it even when they are logged in through the RS232 port and not through the front panel.
To reset the security event log and self-test operands:
1.
Log in as Supervisor (if the role is enabled) or Administrator (if the Supervisor role is disabled) and execute a clear
security command under Commands > Security > Clear Security.
Syslog format
System logs are produced with the CyberSentry option. The format is as follows.
Security log
— Event identification number (index)
Event Number
— UTC date and time
Date & Timestamp
— 255 chars maximum, but in the security log it is truncated to 20 characters
Username
— Device IP address
IP address
— 16 bit unsigned, of type format F617
Role
Enumeration Role
0
None
1
Administrator
2
Supervisor
3
Engineer
4
Operator
5
Factory
5-24
The use of CyberSentry for devices communicating through an Ethernet-to-RS485 gateway is not
supported. Because these gateways do not support the secure protocols necessary to communicate
with such devices, the connection cannot be established. Use the device as a non-CyberSentry
device.
Users logged in through the front panel are not timed out and cannot be forcefully logged out by a
supervisor. Roles logged in through the front panel that do no allow multiple instances (Administrator,
Supervisor, Engineer, Operator) must switch to None (equivalent to a logout) when they are done in
order to log out.
For all user roles except Observer, only one instance can be logged in at a time, for both login by front
panel and software.
When changing settings offline, ensure that only settings permitted by the role that performs the
settings download are changed because only those changes are applied.
Event Number
Date &
Timestamp
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
button, which resets targets, where targets are errors
RESET
RESET
Username
IP address
CHAPTER 5: SETTINGS
button has special behavior in that it
Role
Activity Value