GE N60 Instruction Manual page 162

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

PRODUCT SETUP
Altitude
Range: 0 to 10,0000 m in steps of 1 m
Default: 0 m
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.altitude. This data attribute is provided
by the protocol to allow the user to declare the geographical position of the device in WGS84 coordinates - altitude.
Prefix for GGIO1
Range: 0 to 7 VisibleString characters
Default:
This setting sets the LN Prefix of the logical node GGIO1 that is described in the GGIO1 section later. Valid characters are
upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.
Prefix for GGIO2
Range: 0 to 7 VisibleString characters
Default:
This setting sets the LN Prefix of logical node GGIO2 that is described in the GGIO2 section later. Valid characters are
upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.
Prefix for GGIO4
Range: 0 to 7 VisibleString characters
Default:
This setting sets the LN Prefix of logical node GGIO4 that is described in the GGIO4 section later. Valid characters are
upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.
Master configRev
Range: 0 to 255 ASCII characters
5
Default:
This data attribute is provided by the protocol to allow the user to declare changes to the semantic of the data model of
the UR. The intent is that the user changes Master configRev each time that the semantic or data model changes, so
that clients can readily detect the change. A semantic change is a logical node getting a new semantic use; for example,
an instance of logical node CSWI is now serving a different physical switch, or an instance of a logical node PDIS is now
used for another zone. A data model change is a change in the presence of logical nodes, data objects, data attributes,
or instance names.
The scope of Maser configRev is the entire relay configuration as the Master logical device is the root logical device.
Similar settings are provided for the other logical nodes; the scope of these other configRev settings is limited to the
corresponding logical device configuration.
paramRev
Range: -2,147,483,648 to 2,147,483,647 in steps of 1
Default: 0
This data attribute is provided by the protocol to make changes to the settings of the N60 apparent to clients. The
Substation Configuration Tool and UR Setup software advance the value of paramRev each time any setting changes.
The N60 increments the value of parmRev when a setting change is made other than through CID file download.
LLN0.Mod.ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: sbo-with-normal-security
This setting specifies the control service that clients must use to control the TEST MODE FUNCTION of the N60. An "on"
control to <LDName>/LLN0.Mod changes TEST MODE FUNCTION to Disabled, an "on-blocked" control changes it to
Forcible, and a "test/blocked" changes it to Isolated.
IEC/MMS TCP PORT NUMBER
Range: 0 to 65535 in steps of 1
Default: 102
This setting allows the user to change the TCP port number for Manufacturing Message Specification (MMS) connections.
It is recommended that this setting be left at the default value.
5-46
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS