CHAPTER 5: SETTINGS
Values are transmitted as unsigned 32-bit integers.
Transmission of values occurs once every 250 ms. This is defined as the integrity period. FlexLogic trigger checks are
performed once per power system cycle. Once a deadband or FlexLogic trigger occurs, the next transmission does not
occur until the next 250 ms integrity time-out.
5.9.8.2 Direct integer outputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INTEGERS  DIRECT INTEGER OUTPUTS  DIRECT INTEGER 1(16) OUTPUT
 DIRECT INTEGER 1
 OUTPUT
The direct integer outputs share the direct input and output settings for device ID, data rate, ring configuration, and
channel crossover.
— This setting selects the FlexInteger parameter used to drive the associated direct integer output.
INTEGER 1 VALUE
— This setting selects the FlexLogic operand used to trigger the transmission of the associated direct
INTEGER 1 TRIGGER
integer output. Transmission occurs on the rising edge of the operand. The operand must transition from 0 to 1 and remain
at a value of 1 for at least one power system cycle to ensure detection of the rising edge and transmission of the
associated direct integer output.
5.9.8.3 Direct integer inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INTEGERS  DIRECT INTEGER INPUTS  DIRECT INTEGER 1(16) INPUT
 DIRECT INTEGER 1
 INPUT
The direct integers feature allows the transmission of integer values between any two UR-series devices supporting the
feature. The communication channel is the same as that used for the direct inputs and outputs feature. When the direct
inputs/outputs, direct analogs, and direct integers features are used together on the same channel, the UR-series devices
must be using firmware version 5.70 or higher.
The settings for direct integer input 1 are as follows. The description applies to all 16 direct integer inputs.
— This value selects the source of the direct integer 1 input. Direct integer input 1 is driven by the
DIRECT INTEGER 1 DEVICE
device programmed in this setting.
— This value specifies which input to extract the value for the direct integer 1 input. Direct
DIRECT INTEGER 1 NUMBER
integer input 1 is driven by the input programmed in this setting. This setting value corresponds to the direct integer output
number of the sending device.
— This setting specifies the value of direct integer input 1 when the associated direct device is
DIRECT INTEGER 1 DEFAULT
offline and the
INTEGER 1 DEFAULT MODE
default mode is set to "Last Known," the value of direct integer input 1 remains at the last received value. This value is
stored as an unsigned 32-bit integer.
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
INTEGER 1 VALUE:
Off
INTEGER 1 TRIGGER:
Off
DIRECT INTEGER 1
DEVICE: 0
DIRECT INTEGER 1
NUMBER: 0
INTEGER 1 DEFAULT:
1000.000
INTEGER 1 DEFAULT
MODE: Default Value
is set to "Default Value." When the associated direct device is offline and the
Range: Off, any FlexInteger parameter.
See Appendix A for complete list.
Range: FlexLogic operand
Range: 0 to 16 in steps of 1
Range: 0 to 16 in steps of 1
Range: 0 to 429496295 in steps of 1
Range: Default Value, Last Known
INPUTS/OUTPUTS
5
5-239