CHAPTER 2: PRODUCT DESCRIPTION
The following types of authentication are supported by CyberSentry to access the UR device:
Device Authentication (local UR device authenticates)
Server Authentication (RADIUS server authenticates)
The EnerVista software allows access to functionality that is determined by the user role, which comes either from the local
UR device or the RADIUS server.
The EnerVista software has a device authentication option on the login screen for accessing the UR device. When the
"Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authenticate the
user. In this case, it uses its built-in roles (Administrator, Engineer, Supervisor, Observer, Operator) as login names and the
associated passwords are stored on the UR device. As such, when using the local accounts, access is not user-attributable.
In cases where user-attributable access is required especially to facilitate auditable processes for compliance reasons, use
RADIUS authentication only.
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
No password or security information is displayed in plain text by the EnerVista software or UR device, nor is such
information ever transmitted without cryptographic protection.
CyberSentry user roles
CyberSentry user roles (Administrator, Engineer, Operator, Supervisor, Observer) limit the levels of access to various UR
device functions. This means that the EnerVista software allows for access to functionality based on the user's logged in
role.
Example: Observer cannot write any settings.
The table lists user roles and their corresponding capabilities.
Table 2-3: Permissions by user role for CyberSentry
Roles
Device Definition
Settings
|---------- Product Setup
|--------------- Security
(CyberSentry)
|--------------- Supervisory
|--------------- Display Properties
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Figure 2-2: CyberSentry user roles
Administrator
Engineer
Complete access Complete access
except for
CyberSentry
Security
R
R
RW
R
See table notes
R
RW
RW
Operator
Supervisor
Observer
Command
Authorizes
Default role
menu
writing
R
R
R
R
R
R
R
See table
R
notes
R
R
R
SECURITY