4 SETPOINT PROGRAMMING
S POWER FACTOR
S [ENTER] for more
If the 469 is applied on a synchronous motor, it is desirable not to trip or alarm on power factor until the field
has been applied. Therefore, this feature can be blocked until the motor comes up to speed and the field is
applied. From that point forward, the power factor trip and alarm elements will be active. Once the power factor
is less than either the Lead or Lag level, for the specified delay, a trip or alarm will occur indicating a Lead or
Lag condition. The power factor alarm can be used to detect loss of excitation and out of step.
GE Power Management
ð
BLOCK PF ELEMENT
ENTER
FROM START: 1 s
ESCAPE

POWER FACTOR

ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
POWER FACTOR LEAD
ESCAPE
ALARM LEVEL: Off
MESSAGE
POWER FACTOR LAG
ESCAPE
ALARM LEVEL: Off
MESSAGE
POWER FACTOR ALARM
ESCAPE
DELAY: 1.0 s
MESSAGE
POWER FACTOR ALARM
ESCAPE
EVENTS: Off
MESSAGE
POWER FACTOR
ESCAPE
TRIP: Off
MESSAGE
ASSIGN TRIP RELAYS:
ESCAPE
Trip
MESSAGE
POWER FACTOR LEAD
ESCAPE
TRIP LEVEL: Off
MESSAGE
POWER FACTOR LAG
ESCAPE
TRIP LEVEL: Off
MESSAGE
POWER FACTOR TRIP
ESCAPE
DELAY: 1.0 s
MESSAGE
469 Motor Management Relay
4.11 S10 POWER ELEMENTS
Range: 0 to 5000 sec., step: 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
Range: 0.05 to 0.99 step 0.01, Off
Range: 0.05 to 0.99 step 0.01, Off
Range: 0.2 to 30.0 sec., step: 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3,
Trip & Auxiliary3
Range: 0.05 to 0.99 step 0.01, Off
Range: 0.05 to 0.99 step 0.01, Off
Range: 0.2 to 30.0 sec., step: 0.1
4.11.2 POWER FACTOR