GE D60 Instruction Manual page 341

Line distance protection system, ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5 SETTINGS
b) GROUND INSTANTANEOUS OVERCURRENT (ANSI 50G, IEC PIOC)

PATH: SETTINGS
GROUPED ELEMENTS
 GROUND IOC1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The ground instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
phasor magnitude.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel may be equipped with a standard or sensitive input. The conversion range of a sensitive channel is
from 0.002 to 4.6 times the CT rating.
NOTE
GE Multilin

SETTING GROUP 1(6)
GROUND IOC1
FUNCTION: Disabled
GROUND IOC1 SIGNAL
SOURCE: SRC 1
GROUND IOC1
PICKUP:
1.000 pu
GROUND IOC1 PICKUP
DELAY:
0.00 s
GROUND IOC1 RESET
DELAY:
0.00 s
GROUND IOC1 BLOCK:
Off
GROUND IOC1
TARGET: Self-reset
GROUND IOC1
EVENTS: Disabled
Figure 5–107: GROUND IOC1 SCHEME LOGIC
D60 Line Distance Protection System
5.6 GROUPED ELEMENTS

GROUND CURRENT
GROUND IOC1(2)
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.000 to 30.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-reset, Latched
Range: Disabled, Enabled
,
Disabled
5
5-209

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents