5 SETTINGS
Users logged in through the front panel are not timed out and cannot be forcefully logged out by a
supervisor. Roles logged in through the front panel that do no allow multiple instances (Administrator,
Supervisor, Engineer, Operator) must switch to None (equivalent to a logout) when they are done in
order to log out.
For all user roles except Observer, only one instance can be logged in at one time, for both login by
front panel and software.
To configure server authentication:
1.
In the EnerVista software, choose device authentication and log in as Administrator.
2.
Configure the following RADIUS server parameters: IP address, authentication port, shared secret, and vendor ID.
3.
On the RADIUS server, configure the user accounts. Do not use the five pre-defined roles as user names (Administra-
tor, Supervisor, Engineer, Operator, Observer) in the RADIUS server. If you do, the UR relay automatically provides the
authentication from the device.
4.
In the EnerVista software, choose server authentication and log in using the user name and password configured on
the RADIUS server for server authentication login.
5.
After making any required changes, log out.
When changing settings offline, ensure that only settings permitted by the role that performs the set-
tings download are changed because only those changes are applied.
Pushbuttons (both user-control buttons and user-programmable buttons) located on the front panel can be pressed by an
Administrator or Engineer role. This also applies to the reset button, which resets targets, where targets are errors dis-
played on the front panel or the Targets panel of the EnerVista software. The reset button has special behavior in that it
allows these two roles to press it even when they are logged in through the RS232 port and not through the front panel.
To reset the security event log and self-test operands:
1.
Log in as Supervisor (if the role is enabled) or Administrator (if the Supervisor role is disabled) and execute a clear
security command under Commands > Security > Clear Security.
PATH: SETTINGS
PRODUCT SETUP
 DISPLAY
 PROPERTIES
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
GE Multilin


DISPLAY PROPERTIES

LANGUAGE:
English
FLASH MESSAGE
TIME:
1.0 s
DEFAULT MESSAGE
TIMEOUT: 300 s
DEFAULT MESSAGE
INTENSITY: 25 %
SCREEN SAVER
FEATURE: Disabled
SCREEN SAVER WAIT
TIME: 30 min
CURRENT CUT-OFF
LEVEL: 0.020 pu
VOLTAGE CUT-OFF
LEVEL: 1.0 V
D60 Line Distance Protection System
5.2 PRODUCT SETUP
5.2.2 DISPLAY PROPERTIES
Range: English; English, French; English, Russian;
English, Chinese
(range dependent on order code)
Range: 0.5 to 10.0 s in steps of 0.1
Range: 10 to 900 s in steps of 1
Range: 25%, 50%, 75%, 100%
Visible only if a VFD is installed
Range: Disabled, Enabled
Visible only if an LCD is installed
Range: 1 to 65535 min. in steps of 1
Visible only if an LCD is installed
Range: 0.002 to 0.020 pu in steps of 0.001
Range: 0.1 to 1.0 V secondary in steps of 0.1
5
5-23