B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 38 of 72)
ADDR
REGISTER NAME
7266
Neg Seq Directional Overcurrent 1 Reverse Limit Angle
7267
Neg Sequence Directional Overcurrent 1 Reverse Pickup
7268
Negative Sequence Directional Overcurrent 1 Target
7269
Negative Sequence Directional Overcurrent 1 Block
726B
Negative Sequence Directional Overcurrent 1 Events
726C
Negative Sequence Directional Overcurrent 1 Offset
726D
Neg Seq Directional Overcurrent 1 Pos Seq Restraint
726E
Reserved (3 items)
7271
...Repeated for Neg Seq Directional Overcurrent 2
Disconnect Switch (Read/Write setting) (24 modules)
B
74A0
Disconnect switch 1 function
74A1
Disconnect switch 1 name
74A4
Disconnect switch 1 mode
74A5
Disconnect switch 1 open
74A7
Disconnect switch 1 block open
74A9
Disconnect switch 1 close
74AB
Disconnect switch 1 block close
74AD
Disconnect switch 1 phase A / three-pole closed
74AF
Disconnect switch 1 phase A / three-pole opened
74B1
Disconnect switch 1 phase B closed
74B3
Disconnect switch 1 phase B opened
74B5
Disconnect switch 1 phase C closed
74B7
Disconnect switch 1 phase C opened
74B9
Disconnect switch 1 operate time
74BA
Disconnect switch 1 alarm delay
74BC
Disconnect switch 1 events
74BD
Reserved (2 items)
74BF
...Repeated for module number 2
Thermal Overload Protection (Read/Write Settings) (2 modules)
7788
Thermal Protection 1 Function
7789
Thermal Protection 1 Source
778A
Thermal Protection 1 Base Current
778B
Thermal Protection 1 K Factor
778C
Thermal Protection 1 Trip Time Constant
778D
Thermal Protection 1 Reset Time Constant
778E
Thermal Protection 1 Minimum Reset Time
778F
Thermal Protection 1 Reset
7791
Thermal Protection 1 Block
7793
Thermal Protection 1 Target
7794
Thermal Protection 1 Events
7795
Reserved (2 items)
7797
Repeated for Thermal Protection 2
Broken conductor detection (Read/Write Settings) (6 modules)
77AA
Broken Conductor 1 Function
77AB
Broken Conductor 1 Source
77AC
Broken Conductor 1 I2/I1 Ratio
77AD
Broken Conductor 1 I1 Minimum
77AE
Broken Conductor 1 I1 Maximum
77AF
Broken Conductor 1 Pickup Delay
77B0
Broken Conductor 1 Block
77B2
Broken Conductor 1 Target
77B3
Broken Conductor 1 Events
77B4
Reserved (2 items)
77B6
...Repeated for Broken Conductor 2
B-46
RANGE
40 to 90
0.015 to 30
0 to 2
0 to 4294967295
0 to 1
0 to 250
0 to 0.5
0 to 1
0 to 1
---
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 65.535
0 to 1
---
0 to 1
0 to 5
0.2 to 3
1 to 1.2
0 to 1000
0 to 1000
0 to 1000
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
---
0 to 1
0 to 5
20 to 100
0.05 to 1
0.05 to 5
0 to 65.535
0 to 4294967295
0 to 2
0 to 1
---
D60 Line Distance Protection System
APPENDIX B
UNITS
STEP
FORMAT
degrees
1
F001
pu
0.05
F001
---
1
F109
---
1
F300
---
1
F102
ohms
0.01
F001
---
0.001
F001
---
1
F001
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
s
0.001
F003
---
1
F102
---
---
---
---
1
F102
---
1
F167
pu
0.01
F001
---
0.05
F001
min.
1
F001
min.
1
F001
min.
1
F001
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
---
F001
---
1
F102
---
1
F167
%
0.1
F001
pu
0.01
F001
pu
0.01
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
---
F001
DEFAULT
90
5
0 (Self-reset)
0
0 (Disabled)
0
63
0
0 (Disabled)
"SW 1"
0 (3-Pole)
0
0
0
0
0
0
0
0
0
0
70
0
0 (Disabled)
---
0 (Disabled)
0 (SRC 1)
80
110
45
45
20
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
200
10
150
20000
0
0 (Self-reset)
0 (Disabled)
0
GE Multilin