GE D60 Instruction Manual page 102

Line distance protection system, ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS
Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the follow-
ing figure.
3
The clock configuration LED status is as follows:
Flashing green — loop timing mode while receiving a valid data packet
Flashing yellow — internal mode while receiving a valid data packet
Solid red — (switch to) internal timing mode while not receiving a valid data packet
The link/activity LED status is as follows:
Flashing green — FPGA is receiving a valid data packet
Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit"
Solid red — FPGA is not receiving a valid packet or the packet received is invalid
3-40
Figure 3–44: STATUS LEDS
D60 Line Distance Protection System
3 HARDWARE
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents