Fault Reports - GE D60 Instruction Manual

Line distance protection system, ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
The real-time clock (RTC) and communication protocol times are not correct unless Local Time is configured for the current
location. When the RTC is synchronized with IRIG-B, Local Time must be configured for the current location or else the
timestamps may not be accurate. Furthermore, times reported in historical records and communication protocols may be
incorrect if the Local Time setting is not configured properly.
The
LOCAL TIME OFFSET FROM UTC
hours. Time zones in the eastern hemisphere have positive values; time zones in the western hemisphere have negative
values. A value of zero causes the relay to use UTC for local time. This setting has two uses. When the system RTC is syn-
chronized with a communications protocol providing only local time or it is free-running, the offset setting is used to calcu-
late UTC from the local time these provide. When the RTC is synchronized with a communications protocol providing only
UTC (such as PTP or SNTP), the time offset setting is used to determine local time from the UTC provided. PTP
ALTERNATE_TIME_OFFSET_INDICATOR TLVs are not used to calculate local time. When a communications protocol
other than PTP provides UTC to local time offset (meaning IRIG-B), that offset is used instead of the local time and daylight
time settings.
The
DAYLIGHT SAVINGS TIME (DST)
Note that when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time
offset and so the DST settings are ignored.
PATH: SETTINGS
PRODUCT SETUP
 FAULT REPORT 1
5
The D60 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well as
the characteristics of the line or feeder, are entered in this menu.
The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in
the FaultReport.txt file includes:
Fault report number.
Name of the relay, programmed by the user.
5-60
setting is used to specify the local time zone offset from UTC (Greenwich Mean Time) in
settings can be used to allow the relay to follow the DST rules of the local time zone.


FAULT REPORTS

FAULT REPORT 1
SOURCE: SRC 1
FAULT REPORT 1 TRIG:
MESSAGE
Off
FAULT REPORT 1 Z1
MESSAGE
MAG: 3.00 
FAULT REPORT 1 Z1
MESSAGE
ANGLE: 75°
FAULT REPORT 1 Z0
MESSAGE
MAG: 9.00 
FAULT REPORT 1 Z0
MESSAGE
ANGLE: 75°
FAULT REPORT 1 LINE
MESSAGE
LENGTH UNITS: km
FAULT REP 1 LENGTH
MESSAGE
(km
): 100.0
FAULT REPORT 1 VT
MESSAGE
SUBSTITUTION: None
FAULT REP 1 SYSTEM
MESSAGE
Z0 MAG: 2.00 
FAULT REP 1 SYSTEM
MESSAGE
Z0 ANGLE: 75°
D60 Line Distance Protection System
FAULT REPORT 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: FlexLogic operand
Range: 0.01 to 250.00 ohms in steps of 0.01
Range: 25 to 90° in steps of 1
Range: 0.01 to 650.00 ohms in steps of 0.01
Range: 25 to 90° in steps of 1
Range: km, miles
Range: 0.0 to 2000.0 in steps of 0.1
Range: None, I0, V0
Range: 0.01 to 650.00 ohms in steps of 0.01
Range: 25 to 90° in steps of 1
5 SETTINGS
5.2.7 FAULT REPORTS
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents