5 SETTINGS
Refer to the Control of setting groups example in the Control elements section of this chapter for group activation.
For user-programmable self-tests for CyberSentry, use the Setup > Security > Supervisory menu instead.
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE
SELF TESTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets. Most
of the minor alarms can be disabled if desired.
When in the "Disabled" mode, minor alarms will not assert a FlexLogic operand, write to the event recorder, or display tar-
get messages. Moreover, they will not trigger the
mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in
chapter 7 for additional information on major and minor self-test alarms.
PATH: SETTINGS
PRODUCT SETUP
CONTROL
PUSHBUTTON 1
MESSAGE
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
GE Multilin
USER-PROGRAMMABLE SELF TESTS
DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
FUNCTION: Enabled
REMOTE DEVICE OFF
FUNCTION: Enabled
FIRST ETHERNET FAIL
FUNCTION: Disabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
THIRD ETHERNET FAIL
FUNCTION: Disabled
BATTERY FAIL
FUNCTION: Enabled
SNTP FAIL
FUNCTION: Enabled
IRIG-B FAIL
FUNCTION: Enabled
PTP FAIL
FUNCTION: Enabled
SFP MODULE FAIL
FUNCTION: Disabled
ANY MINOR ALARM
CONTROL PUSHBUTTONS
CONTROL PUSHBUTTON 1
FUNCTION: Disabled
CONTROL PUSHBUTTON 1
EVENTS: Disabled
D60 Line Distance Protection System
5.2.11 USER-PROGRAMMABLE SELF-TESTS
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
or
messages. When in the "Enabled"
ANY SELF-TEST
5.2.12 CONTROL PUSHBUTTONS
CONTROL PUSHBUTTON 1(7)
Range: Disabled, Enabled
Range: Disabled, Enabled
5.2 PRODUCT SETUP
5
5-69