5 SETTINGS
SETTING
BREAKER RESTRIKE 1
FUNCTION
= Enabled
AND
SETTING
BKR RSTR 1 BLK
= Off
SETTING
BREAKER RESTRIKE 1
SOURCE
= IA
= IB
= IC
SETTING
BKR RSTR 1 BKR OPEN
= Off
OR
SETTING
BKR RSTR 1 OPEN CMD
= Off
SETTING
BKR RSTR 1 CLS CMD
= Off
GE Multilin
SETTING
BREAKER RESTRIKE 1 PICKUP
RUN
RUN
Restrike detection logic
ARMED
Current interruption
detection logic
I
< 0.05 pu
mag
t
for > ¼ cycle
AND
Figure 5–157: BREAKER RESTRIKE SCHEME LOGIC
D60 Line Distance Protection System
SETTING
BREAKER RESTRIKE 1
RESET DELAY
0
0
0
RESET
5.7 CONTROL ELEMENTS
T
RST
FLEXLOGIC OPERANDS
T
BKR RESTRIKE 1 OP A
RST
BKR RESTRIKE 1 OP B
BKR RESTRIKE 1 OP C
T
RST
FLEXLOGIC OPERAND
BKR RESTRIKE 1 OP
OR
834012A1.CDR
5-291