B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 32 of 72)
ADDR
REGISTER NAME
Pilot DUTT (1P) (Read/Write Setting)
67D0
DUTT Function
67D1
DUTT Seal In Delay
67D2
DUTT 1P Number of Communication Bits
67D3
DUTT RX1
67D5
DUTT RX2
67D7
DUTT RX3
67D9
DUTT RX4
67DB
DUTT 1P Target
67DC
DUTT 1P Event
B
67DD
DUTT 1P Block
67DF
Reserved (6 items)
Pilot PUTT (1P) (Read/Write Setting)
67EA
PUTT 1P Scheme Function
67EB
PUTT 1P Rx Pickup Delay
67EC
PUTT 1P Seal In Delay
67ED
PUTT 1P Number of Communication Bits
67EE
PUTT 1P Rx1
67F0
PUTT 1P Rx2
67F2
PUTT 1P Rx3
67F4
PUTT 1P Rx4
67F6
PUTT 1P Target
67F7
PUTT 1P Event
67F8
PUTT 1P Block
67FA
Reserved (5 items)
Pilot Hybrid POTT (1P) (Read/Write Setting)
6820
Hybrid POTT 1P Scheme Function
6821
Hybrid POTT 1P Permissive Echo
6822
Hybrid POTT 1P Rx Pickup Delay
6823
Hybrid POTT 1P Trans Block Pickup Delay
6824
Hybrid POTT 1P Trans Block Reset Delay
6825
Hybrid POTT 1P Echo Duration
6826
Hybrid POTT 1P Echo Lockout
6827
Hybrid POTT 1P Seal In Delay
6828
Hybrid POTT 1P Ground Directional Overcurrent Forward
682A
Hybrid POTT 1P Gnd Directional Overcurrent Reverse
682C
Hybrid POTT 1P Number of Communication Bits
682D
Hybrid POTT 1P Rx1
682F
Hybrid POTT 1P Rx2
6831
Hybrid POTT 1P Rx3
6833
Hybrid POTT 1P Rx4
6835
Hybrid POTT 1P Target
6836
Hybrid POTT 1P Event
68737
Hybrid POTT 1P Echo Condition
6839
Hybrid POTT 1P Weak Infeed
683A
Hybrid POTT 1P Weak Infeed Condition
683C
Hybrid POTT 1P Block
683E
Reserved (3 items)
Pilot Blocking (1P) (Read/Write Setting)
6845
Blocking Scheme 1P Function
6846
Block 1P Rx Coord Pickup Delay
6847
Block 1P Transient Block Pickup Delay
6848
Block 1P Transient Block Reset Delay
6849
Blocking Scheme 1P Seal In Delay
B-40
RANGE
0 to 1
0 to 65.535
0 to 2
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
0 to 4294967295
0 to 1
0 to 1
0 to 65.535
0 to 65.535
0 to 2
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
0 to 4294967295
0 to 1
0 to 1
0 to 2
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 4294967295
0 to 4294967295
0 to 2
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
0 to 4294967295
0 to 2
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
D60 Line Distance Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
s
0.001
F001
---
1
F198
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F300
---
1
F001
---
1
F102
s
0.001
F001
s
0.001
F001
---
1
F198
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F300
---
1
F001
---
1
F102
---
1
F199
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
0.001
F001
---
1
F300
---
1
F300
---
1
F198
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F300
---
1
F199
---
1
F300
---
1
F300
---
1
F001
---
1
F102
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
DEFAULT
0 (Disabled)
0
0 (1)
0
0
0
0
0 (Self-reset)
0 (Disabled)
0
0
0 (Disabled)
0
0
0 (1)
0
0
0
0
0 (Self-reset)
0 (Disabled)
0
0
0 (Disabled)
0 (Disabled)
0
20
90
100
250
0
0
0
0 (1)
0
0
0
0
0 (Self-reset)
0 (Disabled)
0
1 (Enabled)
0
0
0
0 (Disabled)
10
30
90
0