Specifications; Protection Elements - GE D60 Instruction Manual

Line distance protection system, ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

2.2 SPECIFICATIONS

2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated.
FlexLogic operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect
with other protection or control elements of the relay, building FlexLogic equations, or interfacing with other IEDs or
NOTE
2
power system devices via communications or different output contacts. If not specified, operate times are given
here for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
PHASE DISTANCE
Characteristic:
Number of zones:
Directionality:
Reach (secondary ):
Reach accuracy:
Distance:
Characteristic angle:
Comparator limit angle: 30 to 90° in steps of 1
Directional supervision:
Characteristic angle:
Limit angle:
Right blinder (Quad only):
Reach:
Characteristic angle:
Left Blinder (Quad only):
Reach:
Characteristic angle:
Time delay:
Timer accuracy:
Current supervision:
Level:
Pickup:
Dropout:
Memory duration:
VT location:
CT location:
Voltage supervision pickup (series compensation applications):
2-16
mho (memory polarized or offset) or
quad (memory polarized or non-direc-
tional), selectable individually per zone
5
forward, reverse, or non-directional per
zone
0.02 to 500.00  in steps of 0.01
±5% including the effect of CVT tran-
sients up to an SIR of 30
30 to 90° in steps of 1
30 to 90° in steps of 1
30 to 90° in steps of 1
0.02 to 500  in steps of 0.01
60 to 90° in steps of 1
0.02 to 500  in steps of 0.01
60 to 90° in steps of 1
0.000 to 65.535 s in steps of 0.001
±3% of operate time or ±1/4 cycle
(whichever is greater)
line-to-line current
0.050 to 30.000 pu in steps of 0.001
97 to 98%
5 to 25 cycles in steps of 1
all delta-wye and wye-delta transformers
all delta-wye and wye-delta transformers
0 to 5.000 pu in steps of 0.001
D60 Line Distance Protection System
2 PRODUCT DESCRIPTION

2.2.1 PROTECTION ELEMENTS

PHASE DISTANCE OPERATING TIME CURVES
The operating times are response times of a microprocessor part
of the relay. See output contacts specifications for estimation of
the total response time for a particular application. The operating
times are average times including variables such as fault inception
angle or type of a voltage source (magnetic VTs and CVTs).
Phase Element (21P)
30
25
20
15
10
5
0
0%
10%
20%
30%
40%
Fault Location [%]
SIR = 0.1
SIR = 1
SIR = 10
SIR = 20
SIR = 30
50%
60%
70%
80%
837717A1.CDR
GE Multilin